G124038, class C
EN 50131-6:2017 + A1:2021
SES-EMA-RL-T2:2021-04
For every application, a matching power supply unit/charger is available. The individual power supply/charger units are distinguished in particular by their permanent accumulator monitoring, voltage stabilisation and current limitation.
The accumulators used with the energy supply must have been tested and approved by the VdS. For the parallel connection of accumulators, only accumulators of the same type and age and from the same production series may be used. Moreover, the regulations according to DIN VDE 0833-1 must be observed.
Fully electronic, voltage stabilized and current limiting power supply/charger unit for stand by parallel operation with deep discharging protection, battery monitoring and battery defect recognition, designed for max. 26 Ah battery capacity. The power supply can be used with the hazard systems:
- MB-Secure IACP series
- MB-IACP series
- ACS-8 access control systems
The power supply / charger unit provides an integrated BUS-2 interface and can also be used as a remote power supply. Status and fault information is displayed via 14 LEDs. Battery types from 6.5Ah to 26Ah can be selected using DIP switches. Furthermore, two different charging characteristics are available, allowing a maximum current draw of up to 3A total current. A suitable NTC is included in the scope of delivery.
- Highly efficient switching regulator technology for optimum performance and low heat generation
- Cost-efficient due to additional outputs for external loads
- More flexibility through various battery configurations
- Versatile due to BUS-2 interface for remote mounting
- High compatibility with existing systems by standard mounting points
- NTC for battery monitoring already included
- 1 output to panel 3A
- 4 auxilary outputs with 2A / 1A / 1A / 1A
- Up to 2A / 3A continuous current (total)
- All outputs electronically protected, with reset button
- 14 LEDs for status and fault indication
- BUS-2 communication with MB-Secure
- Service and diagnostics over BUS-2
- Permanent battery monitoring of 2 batteries
- Battery types selectable via DIP switch 6.5Ah, 12Ah, 17Ah, 18Ah and 26Ah
- Temperature-guided battery charging voltage
- Voltage stabilized with current limiting
- Deep discharge protection
- Charging connection monitoring
- Battery defect monitoring
- Tamper input
- Suitable for ZG20, ZG2, ZG3.1 and ZG4 housings (part no. 0137xx.xx)